Methodology: every formula, every table, every source
By The BackupSizer Team · Last verified 2026-08-02
This page is the calculator's open book. The tables below are imported from the same data files the calculator executes — they cannot drift from what the tool actually computes. Values marked assumption are ours and are disclosed in the tool's output; everything else traces to the cited source on the date shown.
Educational estimate using a simplified NEC 220.83 method — final sizing must be confirmed by a licensed electrician.
1. Running load
Whole-house mode. Connected load = general lighting and receptacles at 3 VA per sq ft (NEC 220.12) + the running watts of every selected appliance + HVAC. Running load then applies an NEC 220.83(A)-style demand factor: the first 8 kW at 100%, the remainder at 40%. Two disclosed simplifications: we factor the whole connected load including HVAC (the code's 220.83(B) variant takes HVAC at 100% when adding heating/cooling — our approach can size slightly lower for heavy-HVAC homes, which the 80% loading rule cushions), and we fold small-appliance circuits into the 3 VA/sq-ft allowance. Citation basis: EC&M "One-Family Dwelling Unit Load Calculations" (accessed 2026-08-02); the 2026 NEC renumbers 220.83 to 120.83 with a unified table — we cite the method, not the code text.
Essentials mode. No demand factoring. Loads that draw continuously (refrigeration, pumps, fans, lighting, AV) are summed straight. Short-cycle loads (microwave, dishwasher, washer, dryer, range) are excluded from the continuous sum and instead feed the peak check and the duty-cycled energy math. This mirrors how generator wattage worksheets ask "what runs at the same time."
EV charging counts at amps × 240 V (Tesla Wall Connector spec: configurable 12-48 A, up to 11.5 kW). Paused-during-outage EVs are excluded from running load and flagged as requiring a load-management setting.
2. Starting surge
Surge = running load + the largest single motor-start delta (or the largest short-cycle load, whichever is bigger). Air-conditioner starting demand is derived from manufacturer locked-rotor amps using the 30% voltage-dip method: starting VA ≈ LRA × 0.7 × 240 V × 0.7 ≈ 0.49 × LRA × 240. Basis: Goodman GSXN4/GSXN3 condenser spec sheets for RLA/LRA; the voltage-dip method from L. Rozenblat's generator motor-starting reference (generators.smps.us), both accessed 2026-08-02.
A soft starter reduces the modeled start draw by 65% (midpoint of Micro-Air's published "reduces the peak current by 50 to 70%"), floored at the running load. Well and septic pumps without published LRA use the Cummins/Kohler "2-3× running" guidance at 3×; Franklin Electric's AIM manual (Table 5) is stricter for generator sizing of submersible pumps — its minimum generator sizes (2 kW for 1/2 hp, 4 kW for 1 hp, 7.5 kW for 2 hp) are worth checking if a well pump is your largest motor.
| Central AC / heat pump | Running W | Starting W (no soft start) | Duty (outage) |
|---|---|---|---|
| 1.5 ton | 1,600 | 4,130 | 80% (assumption) |
| 2 ton | 2,200 | 4,850 | 80% (assumption) |
| 2.5 ton | 3,000 | 6,940 | 80% (assumption) |
| 3 ton | 4,100 | 10,810 | 80% (assumption) |
| 3.5 ton | 4,500 | 12,960 | 80% (assumption) |
| 4 ton | 5,100 | 12,940 | 80% (assumption) |
| 5 ton | 6,500 | 17,640 | 80% (assumption) |
Running = (compressor RLA + condenser fan FLA) × 240 V, Goodman GSXN4 spec sheets. Starting = 0.49 × LRA × 240 V. Indoor blower counted separately. Accessed 2026-08-02.
3. Appliance table
Starting watts are totals (running + start delta). Chart keys: [HD] Generac-format wattage worksheet (Home Depot 3R0WATTGUIDE); [KO] Kohler sizing chart G18-122; [DOE] energy.gov/DOE typical-wattage data; [CU] Cummins motor-start guidance. All accessed 2026-08-02.
| Load | Running W | Starting W | Duty cycle | Source |
|---|---|---|---|---|
| Refrigerator | 700 | 2,900 | 33% | [HD] wattage worksheet; duty [DOE] energy.gov estimating guide |
| Chest freezer | 500 | 1,000 | 33% | [KO] G18-122; duty [DOE] |
| Sump pump (1/3 hp) | 400 | 1,000 | 15% | [KO] G18-122; duty: documented assumption |
| Sump pump (1/2 hp) | 1,050 | 3,250 | 20% | [HD] wattage worksheet; duty: documented assumption |
| Septic/ejector pump | 1,080 | 3,240 | 5% | Zoeller M267 spec (distributor listing); start 3x [CU] |
| Well pump (1/2 hp) | 960 | 2,880 | 5% | Franklin AIM Table 13; start 3x [CU]; duty derived from EPA WaterSense |
| Well pump (1 hp) | 1,600 | 4,800 | 5% | Franklin AIM Table 13; start 3x [CU]; duty derived from EPA WaterSense |
| Well pump (2 hp) | 2,555 | 7,665 | 5% | Franklin AIM Table 13; start 3x [CU]; duty derived from EPA WaterSense |
| Electric water heater | 4,500 | 4,500 | 30% | [DOE] BSE-301 table; duty: EIA-derived + outage reheat caveat, disclosed |
| Electric range (oven + large burner) | 5,500 | 5,500 | 8% | [KO] G18-122 (oven + 8-inch burner rows); duty: documented assumption |
| Electric dryer | 5,400 | 6,750 | 5% | [HD] wattage worksheet; duty: documented assumption |
| Dishwasher | 1,500 | 3,000 | 5% | [HD] wattage worksheet; duty: documented assumption |
| Microwave (1,000 W class) | 1,000 | 1,000 | 4% | [HD] wattage worksheet; duty: documented assumption |
| Clothes washer | 1,150 | 3,400 | 3% | [HD] wattage worksheet; duty: documented assumption |
| Furnace blower fan | 400 | 450 | 50% | [DOE] furnace-fan rulemaking app 7-C; PSC alternative [HD]; duty: documented assumption |
| Pool pump (1.5 hp) | 2,140 | 6,420 | 25% | Hayward Super Pump manual; start 3x [CU]; duty: documented assumption |
| Window AC (18k BTU / 1.5-ton class) | 1,510 | 4,530 | 80% | Frigidaire FHWC183WB2 spec; start 3x [CU]; duty: documented assumption |
| Internet, TV + AV allowance | 300 | 300 | 100% | DR Power (Generac) worksheet + [KO] + Netgear KB 23003 |
| Lighting allowance (essentials) | 300 | 300 | 100% | Allowance (documented assumption); whole-house mode uses NEC 3 VA/sq-ft instead |
Duty cycles feed runtime/energy math only. The refrigerator's 33% comes from DOE's estimating guidance; pump and outage-condition duties have no authoritative source and are disclosed assumptions, chosen conservative-high.
4. Generator mapping
The recommendation is the smallest air-cooled class where 0.8 × rating ≥ running load and rating ≥ surge. The 80% figure follows Kohler's spec-sheet rating note (standby rating applicable to variable loads averaging 80% of rated power) and standard installer guidance. If no class passes but the running load fits under 26 kW, we recommend 26 kW with a load-managing transfer switch; above that is liquid-cooled, licensed-installer territory and the tool says so. Sizing math uses nameplate LP ratings; the natural-gas derate is displayed, never silently applied. Service check: if generator output amps (kW × 1000 ÷ 240) exceed the service rating, we flag a load-managed transfer switch or service evaluation.
| Class (LP) | NG rating | NG ft³/hr ½/full | LP gal/hr ½/full | MSRP span |
|---|---|---|---|---|
| 10 kW | 9 kW | 101 / 127 | 0.97 / 1.48 | $3,649-4,269 |
| 14 kW | 14 kW | 195 / 256 | 1.81 / 3.07 | $4,569-5,389 |
| 18 kW | 17 kW | 169 / 247 | 1.7 / 3.02 | $5,379-6,229 |
| 22 kW | 19.5 kW | 228 / 327 | 2.53 / 3.9 | $6,119-6,979 |
| 24 kW | 21 kW | 203 / 306 | 2.53 / 3.9 | $6,559-7,399 |
| 26 kW | 22.5 kW | 188 / 333 | 2.06 / 3.63 | $6,989-7,899 |
Representative line: Generac Guardian (only brand covering every rung). Source: Generac 10-18 kW and 20-24 kW Guardian spec-sheet PDFs + 26 kW product pages, accessed 2026-08-02. Kohler/Cummins equivalents are on the comparison pages.
5. Battery mapping
For each system we solve two constraints: enough inverters that continuous output covers the running load (and published surge covers the surge), and enough battery modules that usable energy covers duty-cycled demand × outage hours. Usable energy counts 85% of nameplate for the plug-in class (vendors publish nameplate only — disclosed assumption) and 100% for Powerwall 3 (its 13.5 kWh is AC-side on the datasheet). Where a stack cannot honestly cover the load — multi-day electric heat is the classic case — the tool says so instead of quoting a heroic unit count.
| System | Continuous | Surge | Module | Max stack | Base price |
|---|---|---|---|---|---|
| EcoFlow DELTA Pro Ultra | 7.2 kW | 10.8 kW | 6.14 kWh | 3 × 5 modules | $3,999-5,799 |
| Anker SOLIX F3800 Plus | 6.0 kW | 9.0 kW | 3.84 kWh | 2 × 7 modules | $2,299-2,499 |
| Bluetti Apex 300 | 3.8 kW | 7.7 kW | 2.77 kWh | 3 × 7 modules | $1,599-1,699 |
| Tesla Powerwall 3 | 11.5 kW | 185 LRA | 13.50 kWh | 4 × 4 modules | $13,000-16,500 installed |
Sources: Tesla Powerwall 3 datasheet PDF; us.ecoflow.com; ankersolix.com; bluettipower.com — accessed 2026-08-02. Values only available from retailer listings at verification time are marked TODO-VERIFY in the source code and treated as approximate.
6. Runtime & fuel math
Natural gas: indefinite (utility-supplied); we show the interpolated burn rate. LP: usable gallons = tank × 80% (standard fill/reserve practice); hours = usable ÷ burn rate, interpolating linearly between the published ½-load and full-load figures. Battery: usable kWh ÷ duty-cycled average draw. Portable: anchored to the Westinghouse WGen9500DF (example unit) — manufacturer claim of 8 h at 50% load on the 6.6-gal tank (≈0.82 gal/hr), scaled linearly with load. Linear interpolation is a disclosed approximation; real burn curves are not linear.
7. Cost ranges
Every range requires at least three independent sources (manufacturer pricing + retail listings + installer cost guides) and is presented as a range — never a point estimate. Standby installed: 26 kW $13,000-19,500; 10-14 kW $7,000-11,000; 18-24 kW $9,000-16,000. Portable path: unit $700-1,700 + interlock installed $400-850 (to ~$1,500 with permits in high-labor markets). Maintenance: contracts $250-600/yr, service visits $150-450, DIY kit $25-40. Line-item breakdown: install labor (electrical, placement, commissioning) $1,500-6,000; gas line run $500-2,000 (NG); $800-2,500 (LP with tank); automatic transfer switch hardware (often bundled) $500-1,500; concrete/composite pad + site prep $300-1,200; permit + inspection $100-500.
Full source lists render next to every price in the calculator output. The federal 25D residential clean-energy credit expired 2025-12-31; all battery prices shown are gross.
8. The recommendation rules
Three headline rules fire first: natural gas + day-plus outages + set-and-forget → standby; under-12-hour outages + no gas + quiet constraint → battery; minimize-cost + manual operation accepted → portable. Everything else falls to a transparent score (fuel, outage length and frequency, budget posture, quiet, electric-heat loads, and whether a battery would need an installer-quote-scale stack). When the top two paths land within the tie band, the tool shows a "close call" instead of fake confidence. Portable is excluded outright by the quiet toggle or a set-and-forget budget.
9. What this tool is not
- Not a permit-grade NEC load calculation — it simplifies 220.83 as documented above, and your jurisdiction's adopted code edition governs.
- Not a brand recommender. It maps loads to size classes; brand pages compare published specs only — we test nothing and say so.
- Duty cycles during a real outage vary with weather and behavior; ours are disclosed conservative assumptions, and the energy math inherits them.
- Prices move. Every range carries its verification date, and stale ranges get re-verified rather than quietly kept.
Found an error in a number or a fresher spec sheet? Tell me — corrections ship with a changelog note.